Use romex connectors
where required on metal fixtures 410-28
Contractors have the
responsibility to call for inspections:
Rough
- before any insulation or drywall is installed
Service - building's permanent roof must be installed
Final - before building or residence is occupied
Install smoke detectors
on any permit per OBOA 316 (building code)
With absence of primary
grounding electrode, (city water) install 2nd
ground rod or test as per 250-56, (sandy soil)
Boxes required for all
splices and fixtures including outside lights and
receptacles 300-15
Bond interior metal
water piping on well system as per 250-104 and 250-64
(A) (B) & (E)
GFI fans/lights over
tubs/showers, 110-3 (UL listing)
Ground rods and secure
bracing required for T-poles as per Edison
specifications
Raceways out of side of
meter sockets must have seal rings or meyers hub's
314.15
Drywall screws are not
to be used for mounting meter sockets or A/C
disconnects; not suitable for exterior use (galvanized
required) 110-11
1 (one) service per
building NEC 230-2 (multi family dwellings without
structurally independent fire wall [concrete block,
etc.] considered 1 [one] building)
Cables above joist in
attic storage areas shall be protected by guard strip
NEC 320.23 & 334.23
Grounding electrode
conductors run in metal conduits must have bonding
bushings 250-64 (E)
Seal around service
entrance conduits 110-11
GFI all outside
receptacles including lamp post 210-8
Secure raceways as per
300-11, furnace feed; A/C feed; etc.
Temporary wiring shall conform to ART.527 (do not
back feed service off temporary poles)